Winter design

Heating load is the heat the building loses on one cold winter design day, and so the heat the system must put back to hold the room at its winter temperature. It is worked out as a steady state: no sun, no credit for people, lights or equipment, and the outdoor conditions of the chosen percentile. It needs a city with climate data. When the group is off nothing else in the application changes.

Winter design

Heating

On screen: Heating (calculate heating loads).

The switch for the whole group. Off, only this tick shows and the results carry the cooling load alone.

Setting Value
Default Off
Allowed On or off

Ticked, the rest of the group appears and the results gain a Heating Load tab next to the cooling one.

Qheating = (Σ U × A × ΔTwinter + mair × cp × ΔTwinter) × (1 + margin ÷ 100)

Temperature

On screen: Temperature (winter indoor temperature).

The air temperature the room is held at in winter. It sets the temperature difference behind every heat-loss term.

Setting Value
Default 21 °C
Allowed 16 to 26 °C, shown in the temperature unit chosen in the units setting

A higher setting raises the difference between inside and outside, and so raises the conduction loss and the heat needed for fresh air and leakage.

Humidity

On screen: Humidity (winter indoor humidity).

The relative humidity the room is held at in winter.

Setting Value
Default 30 %
Allowed 20 to 60 %

It sets how much moisture the humidifier must add to the fresh air to bring it up to the room's level.

humidifier moisture = mair × (windoor − woutdoor)

Percentile

On screen: Percentile (winter design percentile).

How extreme the winter design day is.

Setting Value
Default 99.6% (recommended)
Allowed 99.6% or 99%

At 99.6% the design temperature is exceeded on the cold side for only 0.4 percent of the hours in a year; at 99% it is exceeded for 1 percent of them, so the design day is milder and the load smaller.

Supply air

On screen: Supply air (heating supply air temperature).

The temperature of the air the system supplies when heating.

Setting Value
Default 40 °C
Allowed 25 to 60 °C, shown in the temperature unit chosen in the units setting

It is used to check whether the airflow already chosen for cooling can carry the heat the room needs. A warmer supply needs less air. When the room needs more air at this supply temperature than its cooling fan delivers, the Heating Load tab flags it Airflow ↑ and Explain shows the supply temperature that would carry the heat at the cooling airflow.

heating airflow = Qheating ÷ (ρ × cp × (Tsupply − Troom))

Margin

On screen: Margin (heating safety margin).

A margin added on the heat lost through the fabric and to outdoor air.

Setting Value
Default On, 10 %
Allowed 0 to 50 %

Untick it to leave the margin out. It multiplies the loss by one plus the percentage divided by one hundred, as in the first formula above.

Partition ΔT

On screen: Partition ΔT (winter partition ΔT reduction).

How much warmer the space behind a partition that faces unconditioned space is assumed to be than outdoors in winter.

Setting Value
Default 50 %
Allowed 0 to 100 %

It is a percentage of the inside-to-outside difference: 0 uses the full difference, and 100 means the partition loses no heat. The hover text gives an example: 21 °C inside, 5 °C outside and 50 % less, so the space behind is taken as 13 °C.