Heating load is the heat the building loses on one cold winter design day, and so the heat the system must put back to hold the room at its winter temperature. It is worked out as a steady state: no sun, no credit for people, lights or equipment, and the outdoor conditions of the chosen percentile. It needs a city with climate data. When the group is off nothing else in the application changes.

On screen: Heating (calculate heating loads).
The switch for the whole group. Off, only this tick shows and the results carry the cooling load alone.
| Setting | Value |
|---|---|
| Default | Off |
| Allowed | On or off |
Ticked, the rest of the group appears and the results gain a Heating Load tab next to the cooling one.
Qheating = (Σ U × A × ΔTwinter + mair × cp × ΔTwinter) × (1 + margin ÷ 100)
On screen: Temperature (winter indoor temperature).
The air temperature the room is held at in winter. It sets the temperature difference behind every heat-loss term.
| Setting | Value |
|---|---|
| Default | 21 °C |
| Allowed | 16 to 26 °C, shown in the temperature unit chosen in the units setting |
A higher setting raises the difference between inside and outside, and so raises the conduction loss and the heat needed for fresh air and leakage.
On screen: Humidity (winter indoor humidity).
The relative humidity the room is held at in winter.
| Setting | Value |
|---|---|
| Default | 30 % |
| Allowed | 20 to 60 % |
It sets how much moisture the humidifier must add to the fresh air to bring it up to the room's level.
humidifier moisture = mair × (windoor − woutdoor)
On screen: Percentile (winter design percentile).
How extreme the winter design day is.
| Setting | Value |
|---|---|
| Default | 99.6% (recommended) |
| Allowed | 99.6% or 99% |
At 99.6% the design temperature is exceeded on the cold side for only 0.4 percent of the hours in a year; at 99% it is exceeded for 1 percent of them, so the design day is milder and the load smaller.
On screen: Supply air (heating supply air temperature).
The temperature of the air the system supplies when heating.
| Setting | Value |
|---|---|
| Default | 40 °C |
| Allowed | 25 to 60 °C, shown in the temperature unit chosen in the units setting |
It is used to check whether the airflow already chosen for cooling can carry the heat the room needs. A warmer supply needs less air. When the room needs more air at this supply temperature than its cooling fan delivers, the Heating Load tab flags it Airflow ↑ and Explain shows the supply temperature that would carry the heat at the cooling airflow.
heating airflow = Qheating ÷ (ρ × cp × (Tsupply − Troom))
On screen: Margin (heating safety margin).
A margin added on the heat lost through the fabric and to outdoor air.
| Setting | Value |
|---|---|
| Default | On, 10 % |
| Allowed | 0 to 50 % |
Untick it to leave the margin out. It multiplies the loss by one plus the percentage divided by one hundred, as in the first formula above.
On screen: Partition ΔT (winter partition ΔT reduction).
How much warmer the space behind a partition that faces unconditioned space is assumed to be than outdoors in winter.
| Setting | Value |
|---|---|
| Default | 50 % |
| Allowed | 0 to 100 % |
It is a percentage of the inside-to-outside difference: 0 uses the full difference, and 100 means the partition loses no heat. The hover text gives an example: 21 °C inside, 5 °C outside and 50 % less, so the space behind is taken as 13 °C.